• 2014 – ZAMBIA

    330/33/11kV: Lumwana S/S, 330/33/11kV Kalumbila S/S, 330/33/11kV Kansanshi S/S,330/33/11kV, Lusaka West S/S Zambia – protection relays commissioning, ABB Switchgear commissioning, Control and Protection System testing (REL670, RED670, RET670, REJ525, 7SA522, 7SD523, P120, MBCI). Checking the installation and testing the Teleprotection equipment: SWT and NSD.

  • 2014 – KUWAIT – continued

    Retesting all protection relays and bay functionalities together with the final client. Examination of all drawings and documentation. Preparing and wiring different modifications requested by the client. Participating on technical discussions with the client and proposing technical solutions. Onsite maintenance of protection and control relays in power transmission networks including: distance relays schemes fault locators and auto reclose relays, transformer, bus bar and feeder protections, transformer tap changing control, synchronizing control, event and fault recorders. During the general check program, in all 3 substations (Sulayibia 400/300/33 kV, Fintas 400/300/33 kV, Jabriya 400/300/33 kV), all protection relays (RED670, REL670, RET670, REJ525, REB500, Siemens 7SD522, Siemens 7SA522, AREVA P120, AREVA P920, SOLKOR N) were retested. The program also included testing of alarms and measurements to control room and dispatch center, switchgear testing (CB timing, motor currents, interlocking). All tests were witnessed by the client. Besides retesting, modification works were done (alarms, interlocking logic, trip logic) as per client request.

  • 2014 – USA – Mackinac

    Commissioning and testing a 200 MW back-to-back light station to help control power flow enhance grid stability and allow for the integration of additional renewable energy sources. Troubleshooting and commissioning engineer for primary equipment and secondary circuits in HVDC power station Mackinac USA. Commissioning and testing equipment (disconnectors, breakers, earth switches): mechanical adjustments, closing and opening times, contact resistance, signals, interlocks checking with the control system, checking of complete wiring of the protection cubicles. Remedy of defects detected during checking of the secondary circuits, defect list clearance. Commissioning and testing primary equipment: CT, CVT, DOSCT, DVD, Rogowski current transformers.

  • 2014 – SWEDEN

    Holleforsen Hydro Power Plant and Substation – Engineering, testing and commissioning of 1×60 MVA hydrogenerator and 1×110 MVA Autotransformer 231/10/10 kV protection relays.

  • 2014 – SWEDEN

    Brista Power Plant Substattion – Engineering, testing and commissioning of SIEMENS, ABB and SEL protection relays. Configuration and commissioning of SIEMENS Teleprotection equipment.

  • 2014 – SWEDEN

    Degerforsen Hydro Power Plant and Substation – Decommissioning, documentation and re-designing and re-engineering the new relays and panels. Full refurbishment of generator and transformer bay.

  • 2014 – SWEDEN

    Hallby Hydro Power Plant and Substation – REG670, RET670, 80 MVA generator lockout logic change, IEC61850 signal list modification and testing.

  • 2014 – SWEDEN

    Stornorrfors Hydro Power Plant – REG670, Engineering, testing and commissioning, successful SAT 155 MVA hydrogenerator.

  • 2014 – SWEDEN

    FAT for TUNAL, Bogota, Colombia, SVC-U, RET670, RET615. Engineering, testing and commissioning TCR and TSC protection panels.